3/3 Phase Online High-Frequency UPS 10KVA 20KVA 30KVA 4KVA
10-40KVA
3/3 Phase
Power Factor 0.8
10-40KVA Series UPS, is 3-phase in and 3-phase out. It is LCD + LED display real-time monitoring and warning. Transfer time is 0ms at AC to DC or inverter bypass. It is a perfect power solution for data center, industrial automatic, server room, broadcasting and television, finance, government department, etc.
Key Features
1, High-frequency online dual conversion.
2, DSP (digital signal processors) ensures the better quality and high performance.
3, N+X parallel redundancy.
4, Output power factor is 0.8.
5, Single phase grid power input range is wild, 110~300VAC.
6, Battery quantity can be adjusted in 16-20 cells.
7, Charging current can be adjusted in 0.5-6A.
8, Emergency power off (EPO), UPS can be shut off instantly in any sudden emergency.
9, ECO mode can do energy saving.
10, Power factor correction is available in 3-phase input.
11, 3 steps extendable charging mode can optimize battery performance.
12, Pure sinewave output is more stable and reliable.
Specifications
Model | 10K | 20K | 30K | 40K | |
Online type | 3-phase in/ 3-phase out | ||||
Capacity | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | |
Input | |||||
Voltage | 3x400VAC(3Ph+N) | ||||
Voltage range | 190-520VAC (3-phase) at 50% load;305-478VAC (3-phase) at 100% load | ||||
Frequency | 46~54Hz or 56~64Hz | ||||
Power factor | ≥ 0.99@100%Load | ||||
Out put | |||||
Voltage | 3 phase 380VAC(3Ph+N) | ||||
Voltage Range (Battery Mode) | ±1% | ||||
Frequency Range (Synchronize Correction Range) | 46~54Hz or 56~64Hz | ||||
Frequency Range (Battery Mode) | 50Hz±0.1Hz or 60Hz±0.1Hz | ||||
Current Crest Ratio | 3:1(max) | ||||
Harmonic Distortion | ≤ 2% THD (Linear Load); ≦5% THD (Non-Linear Load) | ||||
Transfer Time | AC to DC | 0 ms | |||
Invert to Bypass | 0 ms | ||||
Wave Form (Battery Mode) | Pure Sine Wave | ||||
Efficiency | |||||
Grid mode | 89% | 89% | 89% | 90% | |
Battery mode | 86% | 88% | 87% | 89% | |
Battery | |||||
Standard | battery | 12V/7Ah | |||
Qty | 20 | 20pcsx2 | 20pcsx3 | ||
Charging time | 9hours up to 90% | ||||
Max Charging Current | 1A | 2A | 2A | 4A | |
Charging Voltage | 273VDC±1% | ||||
Long terms | battery | 20pcs (16-20pcs optional) | |||
Qty | |||||
Charging current max | 4A | 4A | 4A | 12A | |
Charging voltage | 273VDC±1% | ||||
Display | |||||
LCD or LED | Load Size, Battery Capacity, Grid Mode, Battery Mode, Bypass Mode, Error Indicator | ||||
Warning | |||||
Battery Mode | Once every 4secs | ||||
Low Battery | Once every second | ||||
Overload | Once every 0.5sec | ||||
Error | Long Beep | ||||
Dimension & weight | |||||
standard | Dimension D x W xH(MM) | 815x250x826 | 815x250x826 | 815x300x1000 | 815x300x1000 |
Weight kgs) | 109 | 164 | 234 | 240 | |
Long terms | Dimension D x W x H (mm) | 592x250x826 | 592x250x826 | 815x250x826 | 815x250x826 |
Weight (kgs) | 38 | 40 | 64 | 71 | |
Environment | |||||
Humidity | 0-95%RH@0-40°C(RH) | ||||
Noise | < 60dB@1m | < 65dB@1m | |||
Communication and Control | |||||
RS-232/USB | Windows2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, MAC | ||||
Optional SNMP | Support SNMP & Networking Controller |